|
Does the sight glass
really need to be full?
A common misconception among refrigeration and air
conditioning technicians involves one of the most likely
misleading components of a cooling system; the sight glass. As
we begin our experiences in the world of troubleshooting and
servicing refrigeration and air conditioning systems, a
question frequently asked by ourselves and the anonymous
helpful voices over the radio or more experienced
technician is "Is the sight glass full?" Although
most of the time a full sight glass is acceptable, there are
many instances where a full sight glass is not only not
necessary, but also detrimental to the compressor and/or the
efficiency of the system.
For example,
in an average residential
split-type system, a full sight glass is probably favorable
due to the
inconsistent ambient operating temperatures of both the
condensing unit and evaporator and the generally high amount
of superheat removed through it's operation. However, in an
office building maintaining a somewhat constant return air
temperature and a moderate heat load, a full sight glass is
not always necessary. In fact, the system may be operating
less efficiently than is possible if it is full. The reason
being that a building of this sort simply doesn't generate
enough heat to cause the desired superheat within the system
to fluctuate enough to use any excess liquid refrigerant. With
a
steady heat load, the expansion valve will allow a steady
amount of liquid refrigerant into the evaporator. As the
condenser air temperature decreases at night or in cooler
weather, the amount of liquid generated through the condenser
increases as well as the sub cooling effect. Meanwhile, the
expansion valve or fixed metering device will maintain flow as
usual to the unchanging return air temperature. The compressor
is then working as hard in a low-load time as it is in a
high-load time and the system continues to remove the same
degree of superheat.
In many larger
package roof-top-units,
there may be 30 feet between the sight glass and the metering
device. A large split system may have 100 feet or more between
the two. A full sight glass may indicate an excess amount of
refrigerant. Now this is not to say that the system won't
operate or that the compressor life will shorten. It is simply
less efficient.
In a low temp.
system such as in kitchen
equipment, especially multi-evaporator no-fan coil systems, a
full sight glass may not only be inefficient, but may also
endanger the compressor's valves by slugging it with liquid
refrigerant. In such a case, an indoor fan-cooled condenser
might be in use. The ambient air around it is likely to be a
fairly constant temperature. The heat load is probably minimal
and unchanging. As one or two or more expansion valves begin
to meter open and closed, the amount of liquid refrigerant
required to maintain the desired superheat will fluctuate,
though slightly. And when the load approaches the desired
temperature, the TXV's range may be exceeded on the low end of
the scale.
Liquid refrigerant will then pass through to the compressor,
slugging it.
Because
there is no fan to force the load through the evaporator, the
degree of superheat will be minimal: around 3-5 degrees. Under
these circumstances, I would recommend reading the
manufacturers' preset superheat adjustment and the amount of
adjustment open or closed that is necessary to approximately
set the TXV to the desired individual evaporator superheat.
Most expansion valves change 1-2 degrees per full turn of the
adjusting mechanism. Then begin to charge the system
monitoring each evaporators' superheat and the superheat of
the system as a whole. Determining the ideal superheats for
each can be tricky and it is always application sensitive. But
as long as the superheat of the system is not lower than the
lowest evaporator's superheat, and is never a negative number,
the compressor will not be slugged with liquid. The sight
glass generally won't fill over approximately 1/3 full at any
time and will operate fully to it's expectations as long as
everything is properly sized. I have found that in this type
of system, the sight glass serves only to indicate the
presence of moisture contamination and confusion if used as a
charging tool.
Mark Yarbrough
http://hvacwebtech.com
|