|
HOSHIZAKI CARE![[hoshiz]](images/hoshiz.gif)
TECH-TIPS
#1
TXV
Diagnostics
Thermostatic
Expansion Valves (TXV) are utilized on all present production
Hoshizaki Machines. Misdiagnosis of the TXV is common
because the symptoms of a bad TXV are: low or no ice
production, possible freeze-up, deformed ice cubes, partial or
improper freeze pattern on the evaporator, long cycle times
and flooding or starving of the evaporator. Since the
symptoms are similar to other failures these items should be
checked thoroughly before condemning a TXV: check the water
system to assure that the evaporator and distribution system
are clean. Remember that lime or calcium scale is
transparent when wet, so check the evaporator to assure a
smooth clean freezing surface. Also check the inlet water
solenoid for leak-by during the freeze cycle. This would add
additional water to the reservoir and more evaporator load.
The air cooled condenser must be clean and have proper air
flow. A water cooled condenser must be clean and have adequate
water flow and proper operation of the water regulating
valve. Other refrigeration system components should be
checked. A liquid line valve which leaks by during harvest, a
partial restriction in the system, a bad condensing pressure
regulator valve (headmaster) or a low capacity compressor can
cause symptoms similar to a bad TXV.
The
refrigerant charge must be correct in order to properly
troubleshoot the TXV. The refrigerant charge is critical and a
high or low charge can cause the TXV to operate improperly.
The proper refrigerant type and charge should be weighed in
according to the name plate rating on the unit. Now that we
have covered items with similar symptoms, lets discuss the
thermostatic expansion valve. The TXV operates as a metering
device and feeds refrigerant to the evaporator. There are
three factors which act together to open and close the TXV to
supply the proper amount of refrigerant to the evaporator.
These three factors are the sensing bulb pressure, the,
evaporator pressure and the valve spring pressure. The
sensing bulb contains a type "C" gas charge and is
attached to the evaporator outlet using stainless steel
clamps. The bulb should be mounted between the 10:00 and 2:00
position on the suction line.
Always check
the mounting and clamps to assure good thermal contact. A
loose TXV bulb could cause liquid flood back, long freeze
cycles or a possible freeze up. This could also cause a high
pressure safety switch trip at the beginning of freeze. This
would be due to excessive refrigerant in the harvest loop
because the TXV does not close down properly during harvest.
This excess refrigerant could cause a high pressure
"spike" at the beginning of freeze to shut the unit
down on the high pressure safety. This could occur
intermittently depending on the operating conditions.
Hoshizaki uses non-adjustable TXV’s which are factory set by
the manufacturer. In normal operation, as the water flows down
the evaporator and is cooled and finally begins to freeze, the
load on the evaporator decreases. As the load decreases, the
suction line temperature will decrease which in turn allows
the bulb pressure to decrease. This decrease in bulb pressure
allows the upward spring to begin closing the diaphragm, thus
maintaining proper refrigerant flow. This is why suction
pressure is higher at the beginning of the freeze cycle, then
gradually decreases as the cycle continues. If the TXV valve
does not open enough, long cycles, and low production may
occur. If the valve opens too much or does not close properly,
flood back and possible compressor damage may
occur.
On a KM
cuber, check the frost line, freeze cycle time and ice fill on
the evaporator to assure proper TXV operation. The frost line
at the end of the freeze cycle will range from the suction
line compressor connection to 1/2 the distance from the
evaporator to the compressor. The normal freeze cycle time is
found on the performance data chart in the KM service
manual. You must know the exact inlet water temperature
to read the chart correctly. Suction pressure (5 minutes into
freeze cycle) and head pressure readings are also found on
this chart. The normal ice fill will be from top to bottom and
at the end of the freeze cycle. The last two passes will have
slightly smaller ice cubes if the refrigerant charge is
correct and the TXV is feeding properly.
Some units
utilize multiple TXV’s. In this case each circuit should be
treated individually as a single pass circuit when
troubleshooting. On a flaker, the TXV maintains a
constant suction pressure and evaporator temperature because
the evaporator load is constant. The frost line will be
consistent and within the same range as the KM cuber. A
quick check for a TXV that is suspected bad is to check the
valve swing. To do this, check the suction pressure 5 minutes
into freeze. Remove the TXV bulb and hold it securely in the
palm of your hand for 2 minutes. Check the suction pressure
and place the bulb in an ice bath for 4 minutes to check to
see if the suction pressure swings at least 10 to 25 psi. A
swing of 5 psi or less would indicate a weak TXV which should
be replaced. Hopefully the information provided here will help
you understand TXV operation, symptoms and trouble shooting
procedures, and assist you in future diagnosis on Hoshizaki
equipment.
![[glass]](images/glass.jpg)
KM Pump Assembly
You Get What You Pay For! How
many times have you heard this statement. Well, taking
a good look at the KM pump assembly will definitely
bring this statement to mind. The KM pump assembly
utilizes a Permanent Split Capacitor (PSC) motor.
The capacitor is located in the control box. Using
a PSC motor provides better starting torque and better
running efficiency. The capacitor along with the dual
winding also give us the capability of reversing the pump
motor for the pump -out cycle. The motor has a thermal
overload protector built into the windings and uses
sealed stainless steel roller bearings which do not require
lubrication. The front end
of the assembly is completely rebuildable. Four
bolts or screws can be removed to access the replaceable
impeller and mechanical seal. These parts are
available individually for replacement if failure occurs.
This is definitely not a throw away assembly, however,
in case of a failed motor, the complete assembly
should be replaced. Providing
this quality pump assembly and mounting the assembly
is a dry compartment away from the damp/moist
conditions in the evaporator section have proven
to extend the service life of the KM unit.
__________________________________________
__________________________________________
Service Seminar Results
This is just a quick update on the 1994 Hoshizaki Training
Season. We have completed out Spring Training
sessions for this year. It is obviously hot outside
and your Service Techs are working fast and furiously.
This year the Hoshizaki Care
Department conducted total
of 64 service seminars which included 2,760 Service
Techs. We are presently gearing up for the Fall by
updating our seminars and material. We look forward
to seeing you at the next service seminar held
near you. Contact your
local Hoshizaki Distributor to
get your name on the
seminar list.
__________________________________________
More
Hoshizaki Tips:
-
TXV
Diagnostics
-
SQUEAKY FLAKER
-
ICE STRIPS
-
SIZING ICE MACHINES
__________________________________________
Danny
Moore Hoshizaki America, Inc. Volume 107
Editor
618 Hwy. 74 South July 14, 1994
Peachtree
City, GA 30269
Care
Facsimile: (800) 843-1056
Visit Hoshizaki's Web site
![[logo]](images/logo.gif)
|